| DESCRIPTION |
TYPE |
Order
No. |
| Uninterruptible power supply
unit
3.4 Ah battery module
7.2 Ah battery module
12 Ah battery module |
QUINT-DC-UPS/24DC/40
QUINT-BAT/24DC/3,4Ah
QUINT-BAT/24DC/7,2Ah
QUINT-BAT/24DC/12Ah |
28 66 24 2
28 66 34 9
28 66 35 2
28 66 36 5 |
| INPUT DATA |
| Nominal input voltage
Input voltage range
Current consumption (No Load/charging/maximum)
Switching threshold
Buffer time - Can be configured
Input fuse
Maximum power dissipation - (Ready/buffer mode) |
24 V DC
22.5 - 30 V DC
0.1 A/2.5 A/42.5 A
Ua < 22 V; dynamic Uin - 1 V/0.1 s
0.5; 1; 2; 3; 10; 15; 20; 30; continuous
Internal, 50 A
20 W/30 W |
| OUTPUT DATA |
| Can be connected in parallel (battery
module) |
Yes, to increase the buffer time |
| OUTPUT DATA IN
NORMAL OPERATION |
| Nominal output voltage
Output voltage
Output current
Current limit
Overload fuse |
24 V DC
Uin
40 A
None
Internal, 50 A |
| OUTPUT DATA IN
BUFFER MODE |
| Nominal output voltage
Output voltage - Maximum
Output current
Current limit
Overload fuse
Level of efficiency - Typical
Remote shutdown |
24 V DC
27.9 V DC
40 A (25 A for 3.4 Ah battery module)
45 A
Electronic
98%
Yes |
| CHARGING |
Charge characteristic curve
End-of-charge voltage
Charge current
Battery/presence check/time interval
Battery/quality test/time interval |
I/U characteristic curve
Temperature compensated
< 2.5 A
60 seconds
180 hours |
| MEMORY MEDIUM |
Nominal voltage
Nominal capacity
Charge current |
External
24 V DC
3.4 Ah, 7.2 Ah, 12 Ah
< 2.5 A |
| SIGNALLING |
Power In OK
Alarm
Battery Mode
Battery Charge |
Green LED
Red LED, floating PDT,
30 V AC/DC, maximum; 1 A, maximum
Yellow LED, floating PDT,
30 V AC/DC, maximum; 1 A, maximum
Yellow LED, flashing, floating PDT,
30 V AC/DC, maximum; 1 A, maximum |
| APPROVALS / STANDARDS |
Electrical equipment of machines
Electrical safety (of IT equipment)
Industrial control equipment
Shipbuilding
Electronic equipment for use in electrical power installations |
EN 60 204 (Surge Voltage Category III)
EN 60950/VDE 0805,
UL/C-UL Recognized UL 60 950
UL/C-UL Listed UL 508
Germanischer Lloyd
EN 50 178/VDE 0160 |
| GENERAL DATA |
Insulation voltage
Input/output to housing:
Mounting position
Degree of protection
Class of protection
MTBF According to IEC 1709 (SN 29 500)
Housing version
Dim (W x H x D) default upon delivery
Dim (W x H x D) rotated 90° - Weight Approximately |
1 kV AC type test
1 kV AC routine test
On a horizontal 35 mm (1.378 in.) DIN rail
EN 60 715
1 kV/1 kV
IP20
II
AluNox (AlMg1), closed
(66 x 130 x 125 mm [2.598 x 5.118 x 4.921 in.])
(122 x 130 x 69 mm [4.803 x 5.118 x 2.717 in.])
0.9 kg |
| CE
Conformance With
EMC Directive 89/336/EEC and Low Voltage Directive
73/23/EEC |